Test or certification item 测试名称:EN 54-11 Manual call points 火灾探测和火灾报警系统 第 11 部分:手动火灾报警按钮(手报/MCP)
Test or certification info 测试和认证相关内容:
EN 54-11测试项目:
1. 动作性能(Type A/B 触发力、动作逻辑);
2. 功能、复位与内置测试机构
3. 500 次动作耐久
4. 供电电压波动
5. 环境:干热、低温、循环湿热、恒定湿热、SO₂二氧化硫腐蚀
6. 机械:冲击、正弦振动、外壳撞击
7. EMC 电磁抗扰度全套
8. IP 防护、标识检查
|
Aspect项目 |
EuropeanUnion (EU)欧盟 |
UnitedStates(US)美国 |
China中国 |
|
Specific Standard for MCP |
EN 54-11 (Manual call points) |
UL 38 (Manual signaling boxes / pull stations) |
No dedicated standalone MCP standard |
|
General Product Standard |
EN 54 series |
UL 38 + UL 864 (control panels integration) |
GB fire alarm device standards (applied) |
|
Wireless/Radio Standard |
EN 54-25 |
No UL-specific wireless MCP standard → FCC compliance required |
National RF regulations + CCC |
|
Certification Requirement |
CE marking mandatory |
UL listing / FM approval required |
CCC certification mandatory |
|
Installation Standard |
EN 54-14 |
NFPA 72 |
GB 50116 |
|
Device Definition |
Defined as MCP with Type A / Type B operation |
Defined as manual signaling box (electrical device activated manually) |
Considered a fire alarm initiating device |
|
Operation Types |
Type A (direct), Type B (indirect with cover) |
Single-action/double-action pull stations |
Similar to international configurations |
|
Performance Testing |
EN 54-11 defines mechanical, environmental, durability tests |
UL 38 defines construction, reliability, signaling performance tests |
Tests defined through GB framework (less device-specific) |
|
Placement Rules |
EN 54-14 guidance |
NFPA 72 specifies location, spacing, and height rules |
GB 50116 prescriptive rules |
|
Typical Installation Locations |
Exits, escape routes |
Within 5 ft of exits, ≤ 200 ft travel distance |
Exits and evacuation routes |
|
Approval Bodies |
Notified Bodies (LPCB, VdS, TÜV) |
UL, FM Global |
CNAS labs + CCC bodies |
|
System Integration |
EN 54-2/EN 54-4 |
UL 864+NFPA 72 integration requirements |
GB 50116 mandatory integration |
|
Market Access Requirement |
CE marking required |
AHJ approval based on UL/NFPA compliance |
CCC required |
图片:
有线-MCP (Manual Call Point)手动报警按钮:

无线-MCP Wireless (Manual Call Point)手动报警按钮:

样本报告: